Concept Design Set · Half-Length Loft Rendition · S-1 + A-1 – A-5

The 24 × 40 Half-Length Loft House

Open vaulted great room on the left half; master suite, kitchen, half bath and laundry tucked under a full-width loft on the right. The build slider is anchored to the owner-reported framed shell so the existing half-loft stays separate from every planned layer and trade that comes next.

Footprint24' × 40'
Main level960 sf
Roof-clear loft deck≈526 sf
Wall plate10'-0"
Ridge beam soffit21'-0"
Roof12/12 gable
A-1 3D Construction Model as-found shell from the 2026-09-02 photo survey + planned conversion · stations estimated, not measured
WARM MODERN CABIN — FINISHED EXTERIOR
Build sequence Finish + commissioning 14 / 14
Planned Complete floors, cabinets, trim, paint, fixtures and devices plus porch decking, exterior stairs, guards and handrails; start up systems, correct punch-list work and complete final inspections.
S-1 Foundation + Main Floor Framing Plan continuous footings · 12 discrete CMU stacks · 6-mil ground poly · engineered truss floor
A-2 Main Level Plan 960 sf · entry on the 40' front · scale as noted
A-3 Loft Plan ≈572 sf joist field · ≈526 sf roof-clear deck · ≈284 sf with 5'+ headroom
A-4 Cross Section cut through the loft half, looking toward the master end
A-5 Room + Window Schedules & Notes
RoomGross / finished-clear sizeGross / clear
Great room (living + dining)20' × 24' / 19'-5¾" × 22'-11½"480 / 447.2 sf
Kitchen9' × 16' / 8'-9¾" × 15'-3½"144 / 134.8 sf
Guest half bath4'-6" × 8' / 4'-0½" × 7'-3½"36 / 29.5 sf
Laundry4'-6" × 8' / 4'-0½" × 7'-3½"36 / 29.5 sf
Primary bedroom11' × 14'-6" / 10'-3½" × 13'-9½"159.5 / 141.9 sf
Primary bath7' × 9'-6" / 6'-7½" × 8'-9½"66.5 / 58.2 sf
Walk-in closet4' × 9'-6" / 3'-3½" × 8'-9½"38 / 28.9 sf
Main level24' × 40' gross shell960 / ≈870 sf
Selected loft framing / deck≈572 sf joist field / ≈526 sf roof-clear walking deck≈572 / ≈526 sf
— of which 5'+ headroom≈11'-9⅞" band centered on ridge≈284 sf

Window Schedule · Stock Modules + Gable Cluster

MarkUnit / assemblyQtySill / location

Module code = nominal unit size: 4060 is 4′-0″ × 6′-0″, for example; 3L1260 is a custom three-light fixed assembly. Order and frame only from the selected manufacturer’s unit and rough-opening schedule; these are coordinated design modules, not universal rough openings.

E-1 · Panel Schedule (as modeled)

CktBreakerWireServes
115A AFCI14/2Lights: great room, kitchen, entry, exterior + smokes (14/3 interconnect)
215A AFCI14/2Lights: master, baths + fans, laundry, WIC, loft (3-way at the spiral)
320A AFCI12/2Receptacles: great room + dining
420A AFCI12/2Receptacles: master bedroom + loft
520A GFCI12/2Kitchen small-appliance 1: counter east + island (conduit in engineered floor-truss chase)
620A GFCI12/2Kitchen small-appliance 2: counter west + fridge
720A GFCI12/2Bathroom receptacles (both baths)
820A12/2Laundry (washer)
930A10/3Dryer receptacle
1040A6/3Range receptacle
1130A10/2Water heater
1225A10/2Mini-split condenser, via exterior disconnect
1320A GFCI WP12/2Exterior receptacles, front + back
1420A GFCI/AFCI12/2Dishwasher, receptacle in adjacent sink base

Runs in the model are drawn in jacket colors: white 14/2 · yellow 12/2 · red 14/3 · orange 10-ga · black 6/3. Receptacles are set to the 12'/6' rule, counters to the 4'/2' rule. This is a wiring plan, not a permit set — box fill, stapling, nail plates, and AFCI/GFCI specifics go to your AHJ and a licensed electrician to verify.

Assumptions made — say the word to change any

  1. Orientation. Entry is on the 40' front wall; "right side" reads as the right half as you face the front door. The master sits at the quiet end, the kitchen in the middle next to the great room.
  2. Roof. 12/12 gable, ridge running the long way: 10' wall plate and a structural ridge around 22'. The finished loft is 10'-10½" above the main-level structural subfloor, leaving about 10'-1½" clear beneath the ridge beam and roughly 232 sf with at least 5' of headroom.
  3. Loft floor at 10'-10½" finished. The joist field is about 465 sf. Subfloor and finish stop where the sloped roof assembly clears them, leaving about 430 sf of roof-clear walking deck. The open edge uses solid low-roof closures and 36" vertical-baluster guards.
  4. Stairs. 5'-0" spiral centered on the ridge line at the loft edge — 14 risers at 9.3" with 30° treads, arriving on a platform face-hung to the doubled loft-edge joist. A radial return protects the open landing edge while the stair-arrival side stays unobstructed; the outer chord remains open to the loft. Its steel center column continues to the ridge, and the dropped beam lands on a flush header carried by two posts. Final stair, landing, guard, and headroom compliance still goes to the local code official and engineer.
  5. Laundry is sized for a stacked washer/dryer; widening it to 5' gets you side-by-side units.
  6. Windows and doors are coordinated with cabinets, appliances, wet areas, and ridge-transfer framing; rough openings still require field verification against the existing shell and selected units.

Structure & systems (as modeled)

  1. Foundation: a continuous perimeter footing plus continuous center footings at x=20 and z=12. Above them are twelve separate 16" × 16" × 16" pier stacks — four stations on each long-side row and four on the center row — with four standard CMUs cross-lapped in each stack. There is no continuous block stem wall. Exterior grade is currently modeled at footing-top elevation so both CMU courses remain visible from the open rear and east sides; a black 6-mil ground vapor barrier covers the underfloor grade, cut and lapped at each stack. Exact pier stations, the block support (if any) on the x=20 transverse footing, footing size, reinforcing, grout, anchorage, frost depth and grade remain owner/engineer-confirmed items.
  2. Wraparound porch: a planned covered L runs across the entry/front wall and around the west great-room gable. Its deck sits 1½" below the main-floor datum on separate concrete supports; a framed hip joins the two 2:12 shed-roof wings below the unchanged main eaves. Porch footings, framing, ledgers, flashing, cedar finish sleeves, closely spaced horizontal guard slats, stair, uplift and drainage remain permit- and engineer-controlled. No skirting is modeled.
  3. Main floor: ¾" structural subfloor over a concept 16" open-web truss system, side-hung between three flush longitudinal girders carried by the discrete pier rows. Supplier-designed end trusses, rim framing, bearing blocks, caps and tie-downs complete the load path. Truss depth, spacing, web layout, hangers and every reserved MEP opening belong on the approved truss shop drawings; field-cutting chords or webs is not allowed.
  4. Walls: 2×6 exterior @ 16" o.c. fastened through the structural floor into engineered rim/blocking (bottom plates cut out at doors), double top plate, king + jack studs with doubled headers and sill cripples at every opening, staggered mid-height blocking; 2×4 interior partitions. Envelope: 7/16" OSB sheathing, housewrap, a smooth warm lower-wall finish, vertical cedar gables and entry bay, dark corner/frieze trim, exterior casings and head flashing at every opening.
  5. Upper loft floor: 2×10 joists @ 16" o.c. front-to-back on the walls and a dropped (3)2×12 beam at mid-span, solid blocking over the beam, hanger at the flush stair header; ¾" T&G subfloor starts and stops at the roof-clear eave cuts (finished floor 10'-10½").
  6. Roof: structural ridge beam transfers at each gable through a post above the engineered high-window header, at mid-span through the spiral's steel column, and at the x=29 transfer wall through a post, squash blocks, the dropped beam, a cripple pack, and the door header/jambs; engineered 2×8 rafters @ 16" o.c. are shifted half a bay from the loft joists, use explicit bearing seats and plumb ridge cuts, and have blocking split around the interlaced joists; OSB deck, synthetic underlayment, matte-charcoal standing-seam metal, drip edge, dark rake boards, vented soffits, gutters + downspouts to splash blocks.
  7. Plumbing: 2×6 wet wall with a 3" stack and roof vent; water heater on a drain pan with T&P discharge; PEX trunk-and-tee distribution (red/blue) in the shallow service cavity and approved floor-truss chases; traps and angle stops at every fixture; two hose bibbs. Gravity DWV stays serviceable below the girders at a true ⅛"-per-foot fall, exits through a clear pier bay, then drops outside the rear footing to the connected cleanout and site sewer.
  8. Electrical: meter base + service mast through the roof, feeder to a breakered 200A panel in the laundry; 14 circuits drawn end-to-end in jacket colors (see the E-1 panel schedule) with code-spaced receptacles, switch legs, a 3-way pair at the spiral stair, and 14/3-interconnected smoke/CO detectors at the bedroom, hall, and both vault levels. Cover plates go on at the finish stage.
  9. HVAC: three-zone mini-split — condenser on a pad out back with a disconnect, wall heads in the great room, master, and loft, line sets run in exterior hide channels; bath fans ducted through the joist bays; dryer and range-hood vents capped on the walls.
  10. Insulation: batts in every exterior stud and gable bay; full-depth closed-cell foam is segmented between rafters and held tight to the roof-deck underside (unvented vaulted assembly) — the Insulation slider stage, with its own layer toggle. Final R-value and condensation control remain climate/code verified.

Gross dimensions are to nominal layout datums; clear dimensions are to modeled finish faces. This is a coordinated conversion concept, not a field survey or stamped permit set. Verify the existing shell, every rough opening, selected equipment, and all structural member/footing sizes before ordering or cutting.